Luminous LD3000 INX Online UPS

GST Invoice AvailableFree Shipping

Priyadarsini is a trusted and authorized supplier of The Luminous LD3000-INX Online UPS which is a high-performance 3 kVA / 2400 W power protection solution designed for critical IT, commercial, and industrial applications. Built on true double-conversion Online technology, it ensures your equipment always runs on clean, stable power—shielding sensitive devices from voltage fluctuations, surges, and outages. With a wide input range of 110–300 VAC, microprocessor-controlled reliability, and input power factor ≥0.99, it delivers consistent performance even in challenging electrical environments.

The LD3000-INX supports emergency power off (EPO), automatic bypass, and generator compatibility, making it ideal for routers, switches, emergency lighting, POS systems, desktops, and critical infrastructure. Its selectable charging current allows flexibility in battery configuration, while pure sinewave output ensures safe operation for all connected loads. Proudly Made in India, the UPS is tender-compliant, GeM-listed, and backed by Luminous’ strong nationwide support network—providing seamless, reliable power when it matters most.

2 Years UPS Warranty1 Year Battery Warranty
Category Parameter Specification
General Brand Luminous
General Product Model LD3000-INX
General UPS Type True Double-Conversion Online UPS
Capacity Rated Capacity 3000 VA / 2400 W
Input Input Voltage Range 110 – 300 VAC
Input Low Line Transfer 160 / 140 / 120 / 110 VAC ±5% (based on load %)
Input Low Line Comeback 175 / 155 / 135 / 125 VAC ±5%
Input High Line Transfer 280 VAC ±5%
Input High Line Comeback 270 VAC ±5%
Input Input Frequency Range 40 – 70 Hz
Input Input Phase Single phase with ground
Input Input Power Factor ≥ 0.99
Input OVCD Protection Cut-off at <100 VAC and >280 VAC
Output Output Voltage 200 / 208 / 220 / 230 (default) / 240 VAC
Output Voltage Regulation ±1% (battery mode)
Output Frequency (Sync Mode) 47–53 Hz (50 Hz) · 57–63 Hz (60 Hz)
Output Frequency (Battery Mode) 50 Hz ±0.25 Hz · 60 Hz ±0.3 Hz
Output Output Waveform Pure Sinewave
Output Harmonic Distortion (Linear Load) ≤ 3% THD
Output Harmonic Distortion (Non-Linear Load) ≤ 6% THD
Overload Protection 100–110% Load Audible warning
110–130% Load Shutdown in 60 sec or transfer to bypass
≥130% Load Immediate shutdown or bypass
Efficiency Efficiency (AC Mode) > 90%
Transfer Time AC → Battery Zero
Transfer Time Inverter → Bypass 4 ms (typical)
Battery Battery Type 12 V SMF / VRLA
Battery DC Bus Voltage 72 V DC
Battery Charging Current 1 A / 2 A / 4 A / 6 A (default), optional 12 A
Battery Charging Voltage 82.1 VDC ±1%
Physical Dimensions (D × W × H) 397 × 145 × 220 mm
Physical Net Weight 7.4 kg
Environment Operating Temperature 0 – 40 °C
Environment Operating Humidity 20 – 90% RH (non-condensing)
Environment Acoustic Noise <50 dBA @ 1 meter
Management & Monitoring Communication Interface Smart RS-232 or USB
Monitoring OS Support Windows 2000–7, Linux, Unix, macOS
Monitoring Optional Interface SNMP for browser-based remote management

Luminous LD3000-INX Online UPS